Clean agent systems

أنظمة الغاز النظيف

Water would ruin a server room, an archive or a control room. Clean agents put the fire out without leaving residue, and the equipment is back in service as soon as the room is vented.

NFPA 2001UL / FM listedCivil Defense ready
Equipment

What we supply & install

Manifolded cylinder bank

Manifolded cylinder bank

UL · FM
UseLarge or multiple rooms
ReleaseDetection + manual pull
Single cylinder unit

Single cylinder unit

ROOM SYSTEM
UseServer and telecom rooms
Discharge≤ 10 s

Choosing the agent

AgentHow it worksDischargeOccupied?Typical use
HFC-227ea (FM-200)Absorbs heat≤ 10 sYesServer & telecom rooms
FK-5-1-12Absorbs heat≤ 10 sYesArchives, museums
IG-541 / IG-55Lowers oxygen60 – 120 sYesData halls, zero residue
CO₂Displaces oxygen~ 60 sNoMachinery, unmanned rooms
AerosolInterrupts chemistrySecondsNoElectrical cabinets

Discharge sequence

Two detectors must agree before the room floods, and people get time to leave.

  1. 0 s

    Detector zone 1

    First alarm, bells ring

  2. Zone 2

    Detector confirms

    Pre-discharge alarm; HVAC and doors close

  3. 30 s

    Time delay

    Occupants leave; abort possible

  4. ≤ 10 s

    Discharge

    Agent floods the room

  5. 10 min

    Hold time

    Concentration held to extinguish