Clean agent systems
أنظمة الغاز النظيف
Water would ruin a server room, an archive or a control room. Clean agents put the fire out without leaving residue, and the equipment is back in service as soon as the room is vented.
NFPA 2001UL / FM listedCivil Defense ready
Equipment
What we supply & install

Manifolded cylinder bank
UL · FMUseLarge or multiple rooms
ReleaseDetection + manual pull

Single cylinder unit
ROOM SYSTEMUseServer and telecom rooms
Discharge≤ 10 s
Choosing the agent
| Agent | How it works | Discharge | Occupied? | Typical use |
|---|---|---|---|---|
| HFC-227ea (FM-200) | Absorbs heat | ≤ 10 s | Yes | Server & telecom rooms |
| FK-5-1-12 | Absorbs heat | ≤ 10 s | Yes | Archives, museums |
| IG-541 / IG-55 | Lowers oxygen | 60 – 120 s | Yes | Data halls, zero residue |
| CO₂ | Displaces oxygen | ~ 60 s | No | Machinery, unmanned rooms |
| Aerosol | Interrupts chemistry | Seconds | No | Electrical cabinets |
Discharge sequence
Two detectors must agree before the room floods, and people get time to leave.
- 0 s
Detector zone 1
First alarm, bells ring
- Zone 2
Detector confirms
Pre-discharge alarm; HVAC and doors close
- 30 s
Time delay
Occupants leave; abort possible
- ≤ 10 s
Discharge
Agent floods the room
- 10 min
Hold time
Concentration held to extinguish